CLIMATE ZONE 2
Wood Frame Walls - Group R Buildings >3 stories
Max. | Stud | Min. Stud Spacing | Cavity Insulation | Continuous Insulation (ci) | Recommended Vapor Retarder Options | Wall Assembly | % better than code U-factor |
|---|---|---|---|---|---|---|---|
0.064 | 2x4 | 16" | 0 | 12 | None or Class III (> 3 perms) | 0.064 | 0% |
11 | 5 | None or Class III (> 3 perms) | 0.063 | 2% | |||
13 | 3.8 | Class III or Class II(r) | 0.064 | 0% | |||
15 | 3 | Class III or Class II(r) | 0.064 | 0% | |||
2x6 | 16" | 0 | 12 | None or Class III (> 3 perms) | 0.062 | 3% | |
19 | 2 | None or Class III (> 3 perms) | 0.057 | 11% | |||
20 | 2 | None or Class III (> 3 perms) | 0.054 | 16% | |||
21 | 2 | None or Class III (> 3 perms) | 0.053 | 017 |
Cold-formed Steel (CFS) Frame Walls - Buildings other than Group R
Max. | Stud | Min. Stud Spacing | Cavity Insulation | Continuous Insulation (ci) | Recommended Vapor Retarder Options | Wall Assembly | % better than code U-factor |
|---|---|---|---|---|---|---|---|
0.077 | 3.625" | 16" | 0 | 10 | None or Class III (> 3 perms) | 0.077 | 0% |
11 | 6 | None or Class III (> 3 perms) | 0.076 | 1% | |||
13 | 5 | None or Class III (> 3 perms) | 0.077 | 0% | |||
15 | 4.5 | None or Class III (> 3 perms) | 0.077 | 0% | |||
≥5.5" | 16" | 0 | 10 | None or Class III (> 3 perms) | 0.077 | 0% | |
19 | 4.2 | None or Class III (> 3 perms) | 0.077 | 0% | |||
20 | 3.8 | None or Class III (> 3 perms) | 0.077 | 0% | |||
21 | 3.6 | None or Class III (> 3 perms) | 0.077 | 0% |
Cold-formed Steel (CFS) Frame Walls - Group R Buildings Only
Max. | Stud | Min. Stud Spacing | Cavity Insulation | Continuous Insulation (ci) | Recommended Vapor Retarder Options | Wall Assembly | % better than code U-factor |
|---|---|---|---|---|---|---|---|
0.064 | 3.625" | 16" | 0 | 12.6 | None or Class III (> 3 perms) | 0.064 | 0% |
11 | 8.5 | None or Class III (> 3 perms) | 0.064 | 0% | |||
13 | 7.5 | None or Class III (> 3 perms) | 0.064 | 0% | |||
15 | 7.2 | None or Class III (> 3 perms) | 0.064 | 0% | |||
≥5.5" | 16" | 0 | 12.6 | None or Class III (> 3 perms) | 0.064 | 0% | |
19 | 7 | None or Class III (> 3 perms) | 0.064 | 0% | |||
20 | 6.3 | None or Class III (> 3 perms) | 0.064 | 0% | |||
21 | 6.3 | None or Class III (> 3 perms) | 0.064 | 0% |
[ADD BUTTONS TO ADDT'L CLIMATE ZONES FOR IECC-C/ASHRAE]
[ADD LINK BACK TO MAIN DEEMED-TO-COMPLY LANDING PAGE - that page will include a general introduction to D-T-C concept, the main graphic, Key Terms to Know, and General Notes + links to Climate Zone options for both code sets]
NOTES
NOTE 1: Cavity insulation material R-values shown represent commonly used air/vapor-permeable products such as fiberglass batts/blown, cellulose, and open-cell spray foam. Check manufacture data or product label for actual R-values.
NOTE 2: Continuous insulation R-values are minimums. Using a greater ci R-value will result in lower U-factor for above-code thermal compliance and improved moisture control. All types of FPIS ci may be used provided the minimum ci R-values are satisfied or exceeded. To determine required thickness of ci refer to FPIS manufacturer R-value data for the specific foam sheathing type and brand. For approximate purposes, the thicknes of FPIS ci can be determined by dividing the required R-value by: 4 R/in (EPS - expanded polystyrene); 5 R/in (XPS - extruded polystyrene; or 6 R/in (polyisocyanurate).
NOTE 3: Interior vapor retarder recommendations are per code and vary depending on climate and insulation ratio. Insulation ratio is the ratio of ci R-value to cavity R-value and the greater this ratio the less thermal bridging impacts the thermal performance of the assembly (e.g., higher effective R-value for total amount of insulation used) and the better moisture is controlled. Interior vapor retarders options for use on walls with FPIS ci as indicated in the table are specified per code to ensure adequate interior drying potential while the insulation ratios control wetting potential. For some assemblies in some climate zone, the code may allow for more vapor retarder options than indicated. But, a maximum of two options are shown that represent an optimal combination of performance and cost.
The vapor retarder options featured in the table are descdribed as follows:
None: No interior vapor retarder required (low perm paints or other interior wall finishes < 3 perms should not be used in CZ 0-2 for any wall including those with or without FPIS ci on the exterior). Where no vapor retarder is feasible it provides the maximum inward drying potential for a wall.
Class III vapor retarder: Vapor retarder paint on interior gypsum applied in accordance with the paint manufacturer's installation instructions to achieve a perm rating of >1 to 10 perms, except where indicated in the table as requiring > 3perms (but still not more than 10 perms) for CZ 0-2.
Class II(r) vapor retarder: A Class II responsive vapor retarder with a standard "dry" perm rating of >0.1 perms to 1 perm and a standard "wet" perm rating of > 1 perm per code (e.g., asphalt Kraft paper).
Class I(r) vapor retarder: A Class I responsive vapor retarder with a standard "dry" perm rating of not greater than 0.1 perm and a standard "wet" perm rating of typically >> 1 perm (e.g., proprietary membranes). A Class I(r) vapor retarder is not a "vapor barrier" in the classic sense because its ??????
TIP: Where a Class I(r) or II(r) vapor retarder is indicated, either a Class I(r) or Class II(r) vapor retarder may be used. However, a Class I(r) vapor retarder will tend to decrease wetting potential and increase drying potential above that possible with a Class II(r) vapor retarder. Also, neither create a "double vapor barrer" assembly when used together with FPIS ci per code. Thus, use of a Class I/II(r) vapor retarder does not trap moisture and promotes drying because these vapor retarders are responsive and become more "vapor open" or permeable to allow drying to the interior. While not required by code for walls without exterior continuous insulation, these types of responsive vapor retarders are perhaps more critical to durable perfrmance of such walls in cold climates (e.g., in climate zones 5-8 a Class I(r) vapor retarder is highly recommended for walls without an adequate amount of exterior FPIS ci).